Artikelen in deze sectie
7101 storing
Oorzaak
Aansluiting van incompatibele binnen- of buitendeel (verkeerde capaciteitscode).
Te controleren
Controleer de capaciteitscodes van de binnen- en buitendelen.
Op de binnendeel SW2 controleren.
Units die de storing kunnen veroorzaken:
- Buitendeel
- Binnendelen
- LOSSNAY
Capaciteit buitendeel
| YNW-A | ||||||
| Model | SW5 | |||||
| 3 | 4 | 5 | 6 | 7 | 8 | |
| P200 | OFF | ON | OFF | OFF | ON | OFF |
| P250 | ON | ON | OFF | OFF | ON | OFF |
| P300 | OFF | OFF | ON | OFF | ON | OFF |
| P350 | OFF | ON | ON | OFF | ON | OFF |
| P400 | ON | ON | ON | OFF | ON | OFF |
| P450 | OFF | OFF | OFF | ON | ON | OFF |
| P500 | ON | OFF | OFF | ON | ON | OFF |
| P550 | OFF | ON | OFF | ON | ON | ON |
| EP200 | OFF | ON | OFF | OFF | ON | ON |
| EP250 | ON | ON | OFF | OFF | ON | ON |
| EP300 | OFF | OFF | ON | OFF | ON | ON |
| EP350 | OFF | ON | ON | OFF | ON | ON |
| EP400 | ON | ON | ON | OFF | ON | ON |
| EP450 | OFF | OFF | OFF | ON | ON | ON |
| EP500 | ON | OFF | OFF | ON | ON | ON |
| EP550 | OFF | ON | OFF | ON | ON | ON |
Capaciteit binnendelen
| Model | SW2 | |||||
| 1 | 2 | 3 | 4 | 5 | 6 | |
| P/M10 | OFF | ON | OFF | OFF | OFF | OFF |
| P/M15 | ON | ON | OFF | OFF | OFF | OFF |
| P/M20 | OFF | OFF | ON | OFF | OFF | OFF |
| P/M25 | ON | OFF | ON | OFF | OFF | OFF |
| P/M32 | OFF | ON | ON | OFF | OFF | OFF |
| P/M40 | OFF | OFF | OFF | ON | OFF | OFF |
| P/M50 | OFF | ON | OFF | ON | OFF | OFF |
| P/M63 | ON | OFF | ON | ON | OFF | OFF |
| P/M71 | OFF | ON | ON | ON | OFF | OFF |
| P/M80 | OFF | OFF | OFF | OFF | ON | OFF |
| P/M100 | OFF | OFF | ON | OFF | ON | OFF |
| P/M125 | ON | OFF | OFF | ON | ON | OFF |
| P/M140 | OFF | OFF | ON | ON | ON | OFF |
| P/M200 | OFF | OFF | OFF | ON | OFF | ON |
| P/M250 | OFF | ON | OFF | OFF | ON | ON |